Permit: T11CM01695

Parcel: 140418240

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
11/16/2011 FIRE SPKLR - FINAL Approved
11/14/2011 FIRE SPKLR - FINAL Denied 1. Lower head in Crypto & Merlin Room head is above ceiling tile.
2. In main electrical room add drop coverage, plans show no drop ceiling when there is a drop ceiling added.
3. In the southeast corner of the building there is a storage room (called out on plans) with a head that is 8 feet off a wall not allowed needs to be 7 feet 6 inches or less.