Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/01/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/10/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK UNDER SLAB FOR KITCHEN ISLAND |
|
| 11/08/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) NORTH OF MATCH LINE CEILING ALL OK |
|
| 11/04/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) 141 OPEN OFFICE AREA OK 2) BLDG ONE SERVICE OK |
|
| 11/03/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK A/C UNITS ON ROOF |
|
| 11/02/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK FROM SOUTH TO NORTH MATCH LINE |
|
| 11/01/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) EAST HALLWAY AND CONF. ROOM |
|
| 10/31/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK PARTIAL OPEN OFFICE #166 AND ADJOINING OFFICES-NO POWER POLES YET |
|
| 10/28/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) ALL LV CABLING TO BE SUPPORTED TO STRUCTURE WITH APPROVED SUPPORTS PER 725-800 NEC 2) CANNOT LAY ON DUCT WORK, MECH, PLUMBING, ELECTRIC CONDUITS |
|
| 10/13/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK U.G. IN RADIO ROOM 2) OK HARD LID ROOMS #137 & 139 |