Permit: T11CM01678

Parcel: 12212039C


Addresses:

4373 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T11CM01678

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/08/2011 FIRE - FINAL Approved
11/03/2011 FIRE - FINAL Denied All egress doors shall have thumb latch style locks can not use double cylinder keyed dead bolt locks, with the exception of the front main doors you can use double cylinder dead bolt lock as long as you label above door with the following "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUIPED" - this is for main front entrance door only. IFC & IBC 1008.1.8.3 ED 2006. (times 5 doors)