Permit: T11CM01649

Parcel: 12307294C

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/15/2011 MECHANICAL - FINAL Partial Approval 1) AIR BALANCE REPORT OK
2) DUCT SMOKE DETECTOR TEST OK
3) STILL NEED TO RESOLVE CONDENSATE ISSUES AND NEED TO HAVE 1" PIPE OUT OF UNITS
09/15/2011 MECHANICAL - FINAL Approved SMOKE TESTS AND AIR BALANCE REPORTS REVIEWED AND ACCEPTED
09/14/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) PER SECTION 307.1 I.M.C. CONDENSATE SIZE CANNOT BE SMALLER THAN UNIT OUTLET. PROVIDE MINIMUM 1" PIPE FOR CONDENSATE DISPOSAL
2) PROVIDE AIR BALANCE REPORT
3) PROVIDE DUCT SMOKE DETECTOR TEST REPORT
09/07/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*