Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2011 | MECHANICAL - FINAL | Partial Approval | 1) AIR BALANCE REPORT OK 2) DUCT SMOKE DETECTOR TEST OK 3) STILL NEED TO RESOLVE CONDENSATE ISSUES AND NEED TO HAVE 1" PIPE OUT OF UNITS |
|
| 09/15/2011 | MECHANICAL - FINAL | Approved | SMOKE TESTS AND AIR BALANCE REPORTS REVIEWED AND ACCEPTED | |
| 09/14/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PER SECTION 307.1 I.M.C. CONDENSATE SIZE CANNOT BE SMALLER THAN UNIT OUTLET. PROVIDE MINIMUM 1" PIPE FOR CONDENSATE DISPOSAL 2) PROVIDE AIR BALANCE REPORT 3) PROVIDE DUCT SMOKE DETECTOR TEST REPORT |
|
| 09/07/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |