Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2011 | ELECTRIC - ABOVE CEILING | Approved | ||
| 09/01/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/31/2011 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 08/29/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK PARTIAL SALES FLOOR/STILL WAITING FOR TRACK LTG AND PENDENTS, OK LV. |
|
| 08/25/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* FINISH PRECIOUS ITEMS |
|
| 08/23/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT UDV CABELING 300.11, 725.8, 800.24 2) FILL UNUSED OPENINGS IN BOXES AND CONDUITS 110.12 3) CONTRACTORS TO BE LISTED NOT RECOGNIZED COMPONENTS 110.3 4) VERIFY DE RATING OF CONDUCTORS 310.15 5) SEVERLY ATTACH FIXTURES TO GRID 410.16 AND SUPPORT TRACK SUPPORT PER 410.104 CHECK BOX FILL SHOWROOM OUTLETS |