Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - PRE SLAB
Permit Number - T11CM01642
Inspection Description - PLUMBING - PRE SLAB
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/30/2011 | PLUMBING - PRE SLAB | Approved | IVRS - Inspection :* | |
08/23/2011 | PLUMBING - PRE SLAB | Not ready for Inspection | IVRS - Inspection :* 1) UPL REQUIRES THAT PIPING BE LAID ON A FIRM BED. BRIDGING NOT PERMITTED 2) FENDLE THREADED GLAKE TEE NOT PERMITTED HORIZONTALLY BELOW GRATE. IT IS NOT A DRAINAGE FITTING. USE APPROVED DRAINAGE FITTING. FITTINGS TO BE INSTALLED IN THE DIRECTION OF FLOW 3) STAND PIPE RECEPTOR P-TRAP TO BE ROUGHED IN NO LESS THAN 6" ABOVE GRADE NOR MORE THAN 18" ABOVE GRADE. GROUND PIPE TO BE 18" - 30" IN LENGTH 4) REMOVE SANTE BELOW SLASHER BOX 5) VERFICAL BY HORIZONTAL CHANGE OF DIRECTION TO BE ---GRANCH OR SWEEP. 6) ALL STRAPS AND SUPPORTS TO BE APPROVED PIPE. THERE IS NO LISTING FOR PLUMBING TAPE. |