Permit: T11CM01642

Parcel: 105110660

Inspection Status: Approved

Inspection History: PLUMBING - PRE SLAB

Permit Number - T11CM01642

Inspection Description - PLUMBING - PRE SLAB

Inspection Status - Approved

Date Description Inspector Results Comments
08/30/2011 PLUMBING - PRE SLAB Approved IVRS - Inspection :*
08/23/2011 PLUMBING - PRE SLAB Not ready for Inspection IVRS - Inspection :*
1) UPL REQUIRES THAT PIPING BE LAID ON A FIRM BED. BRIDGING NOT PERMITTED
2) FENDLE THREADED GLAKE TEE NOT PERMITTED HORIZONTALLY BELOW GRATE. IT IS NOT A DRAINAGE FITTING. USE APPROVED DRAINAGE FITTING. FITTINGS TO BE INSTALLED IN THE DIRECTION OF FLOW
3) STAND PIPE RECEPTOR P-TRAP TO BE ROUGHED IN NO LESS THAN 6" ABOVE GRADE NOR MORE THAN 18" ABOVE GRADE. GROUND PIPE TO BE 18" - 30" IN LENGTH
4) REMOVE SANTE BELOW SLASHER BOX
5) VERFICAL BY HORIZONTAL CHANGE OF DIRECTION TO BE ---GRANCH OR SWEEP.
6) ALL STRAPS AND SUPPORTS TO BE APPROVED PIPE. THERE IS NO LISTING FOR PLUMBING TAPE.