Permit: T11CM01642

Parcel: 105110660

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T11CM01642

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/22/2011 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
11/18/2011 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED CLEAR AND LEGIABLE PANEL DRIECTORY 408.4
2) CLAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANEL
3) BOXES MORE THHN 1/4" 314.20
4) NEED TO SEE PEDICURE CHAIRS TO VERIFY LISTING
5) RECEPT IN UTILIY ROOM TOP BE GFCI PER PLANS
6) WHERE IS EXHAUST FAN ?