Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HYDRONIC PIPING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2012 | MECHANICAL - HYDRONIC PIPING | Approved | IVRS - Inspection :* | |
| 10/31/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* | |
| 10/24/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) 100 PSI TEST ON CHILLER AND HOT WATER REHEAT PIPING AND FITTINGS-OK TO CONNECT TO EXISTING 2) RECALL FOR INSPECTION FOR TIE IN TO EXISTING |
|
| 10/21/2011 | MECHANICAL - HYDRONIC PIPING | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE TESTED FITTINGS PRIOR TO THRUST BLOCK FOR INSPECTION |
|
| 10/19/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* |