Permit: T11CM01629

Parcel: 14022002A


Addresses:

1725 E BILBY RD


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T11CM01629

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
04/17/2012 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
12/30/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) NO PULL BOX PER PLANS
2) OK 300' FROM (13.8K) TO LAST CONNECTION (NOTE: 190 DEGREE OF BENDS VISIBLE)
3) OK 2-3" PVC 30' FROM BLDG
11/04/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
10/31/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK IN SLAB WEST CENTRAL BLDG
10/24/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) FROM WEST BLDG TO EAST BLDG UNDERGROUND OK
10/19/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK BRANCH HOMERUNS, PANEL FEEDERS ELECTRIC ROOM TO WALLS (INTERIOR)
10/13/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK PAD AND U.G. FOR PMT #5