Permit: T11CM01609

Parcel: 13613001U

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T11CM01609

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/11/2012 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
05/09/2012 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/18/2012 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/12/2012 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) EARLY AM INSPECTION REQUESTED-8 AM PROVIDED FOR JEFF M.
2) PVC MAYNOT BE GLUED TO ABS INSIDE BLDG 707.1
3) THROUGH DRAINS NOT PROPERLY CONNECTED TO TAIL PIECE
4) ALIGN P TRAP AND TAIL PIECE AND USE APPROVED FITTINGS
04/11/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) RWL BLDG TO CURB TERMINATION
2) OK TO COVER
03/29/2012 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/22/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SHOWER PAN LINERS OK TO COVER
03/16/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SOIL PIPING FOR POOL DECK DRAINS WITH TEST OK
2) RED LINE CHANGE OF ROUTING ON APPROVED PLANS
3) NOTE: POOL PERIMETER DECK DRAINS MUST HAVE 2" CONNECTION AS SHOW ON PLAN
03/15/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ROOM 127, 144 AND 145 OK
02/28/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) TO MUCH WATER AT NORTHEAST CORNER
2) ROOF DRAINS AT BASKETBALL COURT OK
3) UTILITY ROOM/RESTROOM OK FOR INSULATION
4) ADD HANGER
02/15/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) MENS AND WOMENS RESTROOM AND LOCKER ROOMS, OK TO COVER WALLS AND HARD LIDS
02/09/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/26/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) HBS AT COLUMN F AND COLUMN A OK TO COVER
2) DWV IN EQUIPMENT ROOM WALL WITH TEST THRU ROOF OK
01/24/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) YOU MAY NOT INSULATE ON CENTER 1 SIDE PRIOR TO DWV TESTING
2) 3/4" CLEANOUT TO HB AT FRONT ENTRY WITH TEST OK
3) 3" RD AND OD AT COLUMN G OK
01/20/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) VTR AT #7 POOL DRAIN WITH TEST OK
2) RWLS IN MASONRY WITH TEST OK, SUBJECT TO APPROVAL OF MATERIAL TYPE