Permit: T11CM01609

Parcel: 13613001U

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Permit Number - T11CM01609

Inspection Description - REINFORCED MASONRY PRE-GROUT

Inspection Status - Approved

Date Description Inspector Results Comments
04/04/2012 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
01/26/2012 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) ROTUNDA AT 34' TOPPED OUT; GL: 12/C-E OK TO GROUT AND CAP PROGRESS AREA
01/25/2012 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) ROTUNDA AT 32' OK TO GROUT
2) ALL INTERIOR COLUMNS-DRY PACKED AND IN-FILLED
01/24/2012 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) SITE WALL SOUTHEAST CORNER-TOPPED OUT-OK TO GROUT AND CAP
2) ROTUNDA WALL AT 28' 8" OK TO GROUT
01/20/2012 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALL AT 20' 8"; GL: 12/B-C.5; TRASH ENCLOSURE TOPPED OUT: OK TO GROUT PROGRESS AREAS AND CAP ENCLOSURE
01/17/2012 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) NORTH WALL COLUMNS: E-4 AT 16' 8" (A.5-C.5); W AT 20' 4"
01/13/2012 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) NORTH WALL AT 17' 4" AFFE GL: 12-2/G-E; A.5-C GROUTED
01/12/2012 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
1) CONTRACTOR CANCELLED
01/11/2012 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
REAR SITE:
1) WALL (EAST TO SOUTHWEST CORNER-EXCEPT FOR SOUTHEAST CORNER) TOPPED OUT, EAST PIER WALL AT 21' GL: A/10-12; COLUMNS AT NORTH WALL; 4 AT 14' 8" GL: 12/B-C; 4 AT 16' 4" GL: 12/E-G OK TO GROUT PROGRESS AREAS
01/10/2012 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) NORTH COLUMNS GL: 12/A.5-C AT 12' 8"; 12/E-G AT 16' 8"
01/09/2012 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
01/06/2012 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALLS AT 34'-GL: 9.5/C-E, C/10-12, E.5/10-12
2) CMU WALLS AT 32'-GL: 12/C-E.5
3) OK TO GROUT PROGRESS AREAS
01/05/2012 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) MASONRY COLUMNS AT 20' 8" GL: I/10-11; 3 COLUMNS AT 12' GL: 12/E.5-G OK TO GROUT PROGRESS AREAS
01/04/2012 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) RUTUNDA WALLS-N AT 28' 8"-EAST, WEST AND SOUTH AT 32'-2 COLUMNS AT MAIN ENTRY AT 8'-OK TO GROUT PROGRESS AREAS
01/03/2012 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 2ND LIFT ON NORTH COLUMNS AND STEM AT SOUTHEAST CORNER
12/29/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
12/28/2011 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER CONTRACTOR
12/27/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 6 PIERS NORTH SIDE 1ST LIFT WALLS TO 24' AND MLT 3 AT ENTRY TO 24' EAST AND WEST ROTUNDA-SPECIAL INSPECTED
12/21/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) NORTH WALL EAST AND WEST SIDES TO ENTRY TOP OUT
2) 40' EAST AND WEST WALLS FROM NORTH CORNERS TOP OUT
12/20/2011 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
1) RAINED OUT
12/19/2011 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
1) RAIN
12/16/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) NORTH WALL EAST 1/2 AND EAST WALL RETURN 50' TO 24' 8"
2) I 10-2 TO 12
3) 12 I TO E TOP OUT
12/15/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) WEST INTERIOR WALL TOP OUT, WEST EXTERIOR WALL AND NORTH WALL WEST 1/2 TO 24' 8"
2) OK WITH COMPLIANT SPECIAL INSPECTION
12/12/2011 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
1) CONTRACTOR CANCELLED-RAINED OUT
12/09/2011 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
1) CONTRACTOR CANCELLED
12/08/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALLS AT 20' 8", GL: A/10-12; 12/A-D OK TO GROUT PROGRESS AREAS
12/07/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALLS AT 24' 4"; GL: I/10-12, 12/E-I OK TO GROUT PROGRESS AREAS
12/06/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) WEST CMU WALL (PARAPET LEVEL) 27' 4" OK TO GROUT, GL: I/1-12
12/05/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALLS AT 16' 8"; GL: A/10-12, 12/A-D.5 POP OUTS (EAST) AT 14' 8"-OK TO GROUT PROGRESS AREAS
12/02/2011 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
1) RAINED OUT
12/01/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALLS AT 24' 8", GL: I/11-12, 12/E-I OK TO GROUT PROGRESS AREAS
11/30/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALLS AT 12' 8" AFFE; GL: A/10-12, 12/A-D OK TO GROUT PROGRESS AREAS
11/29/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALL AT 26' 4" AFFE, GL: I/1-5; CMU WALL AT 24' 8" AFFE GL: I/5-10 OK TO GROUT PROGRESS AREAS
11/28/2011 REINFORCED MASONRY PRE-GROUT Partial Approval 1) CMU WALLS AT 12' AFFE: GL I/11-12, 12/E-I OK TO GROUT PROGRESS AREA
11/24/2011 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALL AT 24'
GL 1/C-I OK TO GROUT PROGRESS AREA
11/22/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALLS AT 8' GL: A/10-12; 12/A-D OK TO GROUT PROGRESS AREAS
11/21/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALLS AT 8' GL: I/11-12; GL: 12/E-I OK TO GROUT PROGRESS AREA
11/18/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALLS AT 4' A.F.F.E. GL: I/11-12; GL: 12/E-I OK TO GROUT PROGRESS AREAS
11/18/2011 REINFORCED MASONRY PRE-GROUT Partial Approval 1) CMU WALLS AT 4' A.F.F.E.; GL: A/10-12 12/C.5-A OK TO GROUT PROGRESS AREAS
11/16/2011 REINFORCED MASONRY PRE-GROUT Partial Approval 1) CMU WALLS AT 24' 4"-27" GL: A/1-10; 1/A-F OK TO GROUT PROGRESS AREAS
11/15/2011 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER CONTRACTOR
11/14/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALL AT 24' 8" AND 22' 8" GL: 1/A-I OK T GROUT PROGRESS AREAS
11/10/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALL AT 20' 8" GL: I/2-11 OK TO GROUT PROGRESS AREAS
11/09/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALL AT 20' 8"-GL: A/1-9.75 BEARING PLATES, LEDGER BOLTS, HOLD DOWNS (STRAP) OK TO GROUT PROGRESS AREAS
11/07/2011 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
1) RAINED OUT
11/03/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALLS AT 20' 8" GL: A/1.5-10.5; I/1-6
11/01/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALL AT 20' 8" GL: 1/A-I; POCKETS AS PER DETAIL #315, PAGE S602 OK TO GROUT PROGRESS AREAS
10/28/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALL AT 16' 8" GL: I/1-5, I/6.5-11 BOND BEAM AT WINDOWS 17' 6" I/5-6 OK TO GROUT PROGRESS AREAS
10/27/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALL AT 16' 8", GL: 1/A-I OK TO GROUT
10/26/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALLS AT 16' 8" GL: A/1-9.5; 1/A-B OK TO GROUT PROGRESS AREA
10/25/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALL AT 12' 8"; GL: 1/B.5-I OK TO POUR PROGRESS AREA
10/24/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALLS AT 12' 8"; GL: A/1-11; 1/A-C OK TO GROUT PROGRESS AREAS
10/21/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALLS AT 4' 8"-8' 8"; GL: 1/C.8-I; I/1-10.5; OK TO GROUT PROGRESS AREAS
10/20/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) STEM WALLS GL: 12/A-I-COLUMNS INCLUDED OK TO GROUT PROGRESS AREAS
10/19/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALL AT 8'-8" AFFE: GL: A/1-9.5 OK TO GROUT PROGRESS AREAS
10/18/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) SOUTH CMU WELL 1/C-I AT 0"-48" AFFE; WEST CMU WALL I/1-10.5 AT 0"-48" AFFE OK TO GROUT PROGRESS AREAS
10/14/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) STEM WALL GL: I/-12 OK TO GROUT
10/13/2011 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALLS GL: A/1-12; 1/A-I AT 4' 8" OK TO GROUT
10/07/2011 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*