Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T11CM01602

Parcel: 305030180


Addresses:

12960 S HOUGHTON RD

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
06/04/2012 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) CONTRACTOR NOT IN TRAILER
2) UNABLE TO LOCATE PLUMBER ON SITE
06/04/2012 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
ACID WASTE REVENT? W/TEST OK, ACID WASTE COMPLETE
DWV W/ TEST THRU ROOF OK
05/29/2012 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/24/2012 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) GAS THRU KIT AREA WITH 60 PSI TEST
05/21/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/16/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) MAIN TOILET ROOMS OK
05/11/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DOMESTIC WATER ADMIN, RUNS 1018-1018 W/ 150PSI TEST
COMPLETION OF ACID WASTE 1ST FLOOR
05/08/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) 1ST LEVEL AND 2ND LEVEL TRS DWV WITH TEST TO ROOF
2) WATER MAINS AND BRANCHES TO FIXTURES 1066-1068
3) ACID WASTE ROOM 1066-1068
05/03/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DOMESTIC WATER SOUTH WITH 100 PSI TEST OK; CLASSROOMS
2) DWV ADMIN NORTH OF C LINE WITH TEST THRU ROOF OK
3) GAS PIPING ADMIN/LIBRARY WITH TEST OK
04/25/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PVC DWV SANITARY SEWER, FIRST AND SECOND FLOOR CLASSROOMS UP PAST REVENT OK (ON 2ND FLOOR)
04/23/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OVER HEAD PVC DWV FOR ROOMS 2008 & 2004, DWV AND REVENTS FOR 1ST FLOOR, #1047 & 1048 WATER AND #1092 & 1094 TEST OK
04/19/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/18/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DOMOSTIC WATER MAINS W/TEST OK
GAS MAINS W/ 100 PSI TEST OK NORTH SIDE
WATER AND SANITARY DWV 1ST & 2ND LEVEL CLASS RMS SOUTH EAST & WEST WING
04/02/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*