Permit: T11CM01602

Parcel: 305030180


Addresses:

12960 S HOUGHTON RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
01/27/2012 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
01/12/2012 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 4" LINE (BCS) AT GL: .5A/1-10.5
01/05/2012 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
01/04/2012 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) G INTERCEPTOR TEST AND CONNECTIONS OK
12/22/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
12/08/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) AW THRU BLDG OK, CALL FOR INTERCEPTOR INSPECTION
11/15/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) WATER TEST GW PER INITIAL AND HIGHLIGHTED PAGE 1P2.3
11/14/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 1074, 1078 AND 1040 WATER TEST PER HIGHLIGHT AND INITIAL 1P1.3 & 1P2.1
11/09/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
11/02/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) ROOMS 1080, 1077, 1082, 1083 AND 1086 PER HIGHLIGHT 1P2.1 DRINKING FOUNTAINS
2) HIGHLIGHTED ROOM 1025 A & B 1P1.3
3) RESTROOM 1071, 1073, 1059, 1062, 1063, 1064 AND 1066 AS HIGHLIGHTED 1P1.2 NOT APPROVED ? ? DATED 9/22/11
10/28/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 2 1/2' WATER IN WALL FOR P-8'S 1025 A & B FITNESS ROOM
2) 3" RISER FOR MECH ROOM 1102 UP AND OUT
10/24/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 3" T/K UP AND OUT SOUTHWEST CORNER 1088 TEST OK
2) POTABLE 1 1/4 FOR EYE WASH AND 3/4 FOR HOSE BIB & DRINKING FOUNTAIN 1088
10/20/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) ROOM 1089, 1090 & 1092 FROM INTERIOR TO 3' EXTERIOR WATER TEST EXCEPT PROVIDE SAN TEE FOR FLOOR SINK DRAIN ARM
2) RECEIVED LETTER FOR OK OF PVC ASTM F-891
10/17/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 3" CDV WATER TEST TO 3' EXTERIOR AS INITIALED 1P1.3
2) 4" SANITARY FROM DOWNSTREAM 3' EXTERIOR UPSTREAM PER HIGHLIGHTED AND INITIALED ON PAGES 1P1.3 & 1P1.2, INCLUDING REVENT IN RESTROOM 1097
3) WATER TEST OK