| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/12/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/07/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE HAIL GUARDS PER PLANS 2) PROVIDE THE T-STAT SPECIFIED IN PLANS 3) PROVIDE AIR BALANCE REPORT 4) PROVIDE CANVAS CONNECTOR COVER ON 4 TON UNIT 5) PROVIDE FIRE RATED PIPE WRAP ON EXPOSED ABS IN PLENIUM CEILING 6) PROGRAM T-STATS FOR FAN TO RUN CONTINOUSLY DURING OCCUPIED HOURS 7) PROVIDE DUCT SMOKE DETECTOR TEST REPORT |