Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T11CM01572

Parcel: 13506136D


Addresses:

2590 S KOLB RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/12/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/07/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE HAIL GUARDS PER PLANS
2) PROVIDE THE T-STAT SPECIFIED IN PLANS
3) PROVIDE AIR BALANCE REPORT
4) PROVIDE CANVAS CONNECTOR COVER ON 4 TON UNIT
5) PROVIDE FIRE RATED PIPE WRAP ON EXPOSED ABS IN PLENIUM CEILING
6) PROGRAM T-STATS FOR FAN TO RUN CONTINOUSLY DURING OCCUPIED HOURS
7) PROVIDE DUCT SMOKE DETECTOR TEST REPORT