Permit: T11CM01554

Parcel: 125100320

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/19/2011 ELECTRIC - INTERMEDIATE Approved
07/18/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* 1) SEPERATE GROUNS & NEUTRALS AT SUB PANEL 250.24
2) ONLY ONE NEUTRAL CONDUCTOR PER TERMINAL 200.8
07/13/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) GROUNDING ELECTRODE
07/06/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) LINE SIDE ONLY
2) NEED 2 GROUND ROD FOR GROUNDING ELECTRODE SYSTEM