Permit: T11CM01550

Parcel: 13507451C


Addresses:

1851 S PANTANO RD


Inspection Status: Partial Approval

Inspection History: PLUMBING - FINAL

Permit Number - T11CM01550

Inspection Description - PLUMBING - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
01/31/2012 PLUMBING - FINAL Partial Approval
01/31/2012 PLUMBING - FINAL Approved
12/23/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PAR APPROVAL OF TI TRMS.
DWV TEST OK.
PIPING WALLS OK.
RECIRE? HW SYSTEM REQUIRES 1" THICK PIPE INSULATION.
SUBJECT TO CITY APPROVED PLAN REV
12/22/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
DWV PIPING IS NOT FULL FOR TEST
ALSO THERE IS YET ANOTHER LEAK ABOVE THE CEILING OF LEVEL 1.
NOT READY FOR THE 5TH TIME IN A ROW.
CONTINUED NOT READY INSPECTIONS WILL RESULT IN RE-INSPECTION FEES.
ALSO, REMOVE WALL INSULATION LEVEL 2
PIPING HAS NOT BEEN TESTED.
YOU WERE NOT GIVENPERMISSION TO ONE SIDE WALLS
1ST LEVEL PIPE INSULATIONS HAS NOT BEEN COMPLETED IN WALLS . SEAL ALL JOINTS
12/21/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
12/20/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) COMPLETE WORK, PROVIDE MATERIAL SPECS
2) INSPECTIONS FOR UN-PERMITTED TI
12/19/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) NO WORK MAYBE COVERED PRIOR TO INSPECTION AND TEST
2) PROVIDE MATERIAL SPECS FOR GAS AND OTHER PIPING & SUPPORTS
3) 10 PSI TEST OK (UNAPROVED T.I.)
12/16/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
10/26/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*