Inspection History Details
Inspection Status: Partial Approval
Inspection History: PLUMBING - FINAL
Permit Number - T11CM01550
Inspection Description - PLUMBING - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/31/2012 | PLUMBING - FINAL | Partial Approval | ||
01/31/2012 | PLUMBING - FINAL | Approved | ||
12/23/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* PAR APPROVAL OF TI TRMS. DWV TEST OK. PIPING WALLS OK. RECIRE? HW SYSTEM REQUIRES 1" THICK PIPE INSULATION. SUBJECT TO CITY APPROVED PLAN REV |
|
12/22/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* DWV PIPING IS NOT FULL FOR TEST ALSO THERE IS YET ANOTHER LEAK ABOVE THE CEILING OF LEVEL 1. NOT READY FOR THE 5TH TIME IN A ROW. CONTINUED NOT READY INSPECTIONS WILL RESULT IN RE-INSPECTION FEES. ALSO, REMOVE WALL INSULATION LEVEL 2 PIPING HAS NOT BEEN TESTED. YOU WERE NOT GIVENPERMISSION TO ONE SIDE WALLS 1ST LEVEL PIPE INSULATIONS HAS NOT BEEN COMPLETED IN WALLS . SEAL ALL JOINTS |
|
12/21/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
12/20/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE WORK, PROVIDE MATERIAL SPECS 2) INSPECTIONS FOR UN-PERMITTED TI |
|
12/19/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NO WORK MAYBE COVERED PRIOR TO INSPECTION AND TEST 2) PROVIDE MATERIAL SPECS FOR GAS AND OTHER PIPING & SUPPORTS 3) 10 PSI TEST OK (UNAPROVED T.I.) |
|
12/16/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
10/26/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |