Permit: T11CM01544

Parcel: 115160470

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
06/10/2011 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
06/09/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) RECEPTS ON INDUTRIAL COVERS TO BE PER 406
2) GROUND JUNCTION BOXES 250.148
3) BOXES MORE THAN 1/4" 314.20
4) BOND JUNCTION BOX ENCLOSURE PER 250.122
5) FINISH VDV AS DISCUSSED 300.11
6) TIGHTEN LOOSE FITTINGS
06/08/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) VDV CABLING TO BE PER 725.3 & 8, 760.3 & 24, 800.3 & 24 AND 300.11
2) SECURE FIXTURE TO GRID SMALL BACK ROOM
05/24/2011 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*