Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T11CM01544
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/10/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
06/09/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) RECEPTS ON INDUTRIAL COVERS TO BE PER 406 2) GROUND JUNCTION BOXES 250.148 3) BOXES MORE THAN 1/4" 314.20 4) BOND JUNCTION BOX ENCLOSURE PER 250.122 5) FINISH VDV AS DISCUSSED 300.11 6) TIGHTEN LOOSE FITTINGS |
|
06/08/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) VDV CABLING TO BE PER 725.3 & 8, 760.3 & 24, 800.3 & 24 AND 300.11 2) SECURE FIXTURE TO GRID SMALL BACK ROOM |
|
05/24/2011 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |