Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2011 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 06/10/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REDUCING WASHERS INSTALLED BACKWARDS 2) PROPERLY SUPPORT CONDUITS ACCROSS ROOF 3) TIGHTEN LOOSE FITTINGS 4) PROVIDE PHYSICAL PROTECTION FOR PV CONDUCTORS 5) SUPPORT PV CONDUCTOR UP OFF ROOF AND UNDER ARRAYS 6) CANNOT GET TO JUNCTION BOX TO INSPECT AND SECURE BOX 7) SUPPORT GROUNDING BOND CONDUCTORS 8) BOND UNIRAC RAILS AS PER MANUFACTURES INSTRUCTIONS (PG25) |