Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 11/14/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) URINALS TO BE MAX 12" AFF TO OVER FLOW 2) LAVATORIES REQUIRE MIXING VALVES-SEE PLUMBING FIXTURE SCHEDULE-LAVITORY NOTES 3) REQUIRE METHOD OF STERILIZATION 4) REQUIRE CLEAN BACTERIA REPORT 5) CERTIFY ALL BACKFLOWS 6) I.W. PIPING REQUIRES CEMENT AND PRIMER 7) I.W. PIPING MAY NOT BE COMBINED 8) FLOOR SINKS REQUIRES ? 9) 1" AIR GAP STRICTLY ENFORCES SUPPORT ALL PIPING 10) MAY NOT BE A COMPLETE LIST 11) HAVE PLUMBER ON SITE AT NEXT INSPECTION 12) CONTINUED NOT READYS MAY RESULT IN A REINSPECTION FEE |