Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T11CM01520
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/14/2011 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/08/2011 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO COVER WALLS 2) FLANGES OK |
|
09/06/2011 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) GAS NOT INSTALLED PER PLAN, NO REVISION ON SITE-OK TO COVER SUBJECT TO REVISED PLAN 2) SUSHI BAR OK TO COVER 3) OK TO INSULATE HOT PIPING 4) CLOSET FLANGES TO EXTEND 1/4" ABOVE FINISHED FLOOR 5) HAMMER ARRESTORS REQUIRED ON FAST CLOSING VALVES (URINAL) |
|
08/30/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) AT P-2 VERIFY WASTE IS TO GREASE WASTE, P-2 REQUIRES FULL SIZE CLEANOUT 2) DO NOT COVER ANYTHING UNTIL IT HAS BEEN INSPECTED AND APPROVED 3) SUPPORT ALL STUB OUTS 4) CAP OFF ALL OPEN PIPING 5) TEST ALL PIPING 6) SUPPORT VERTICAL AND HORIZONTAL PIPING |