Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T11CM01520
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/28/2011 | ELECTRIC - FINAL | Approved | ||
11/23/2011 | ELECTRIC - FINAL | Denied | 1. COLD TABLE TO BE INSTALLED TO INSPECT 2. EM LIGHTS & EXIT SIGN NOT WORKING 3. REINSPECTION FEE HAS NOT BEEN PAID |
|
11/14/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CONTRACTOR TO MAINTAIN LOCK OUT/TAG OUT UNTIL FINA CLEARANCES 2) DO NOT OPERATE WITHOUT CLEARANCES 3) OK SUSHI COUNTER WIRING AND DEVICES 4) OK POWER WIRING UNDER COUNTERS |
|
11/09/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DERATE PER 310.15 2) LABEL FLOOR BOXES TO CIRCUITS 408.4 3) LABEL PANEL COVER 4) ENTER SECTION SERVED 408.3 5) FILL UNUSED OPENINGS 6) NEED APPROVED LIVE END FOR TRAC LIGHTS 7) BOXES MORE THAN 1/4" 314.20 OR 1/8" 314.21 8) CLEAN FOREIGN MATERIAL AND DIRT FROM BOXES 9) NEED TO SEE SUSHI COUNTER WIRING 10) NO POWER TO WELLS UNIT OR TABLES ADJACENT 11) VERIFY LISTING FOOD TABLES 12) LOOSE FITTINGS 13) PARTIAL INSPECTION-CHECK ROOF NEXT TIME |