Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T11CM01520
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/28/2011 | ELECTRIC - INTERMEDIATE | Approved | ||
10/13/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
09/15/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS AND LIDS FOR DRYWALL 2) NOTE: BOX ACCESSIBILITY |
|
09/14/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection 1) FINISH PREVIOUS ITEMS WITH SHAFFER ELECTRIC 2) PLEASE PAY REINSPECTION FEE BEFORE NEXT INSPECTION |
|
09/09/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) TIGHTEN LOOSE FITTINGS AND MISSING SET SCREWS 2) FILL UNUSED OPENINGS IN JUNCTION BOXES 3) UNCOVER ALL AREAS COVERED WITHOUT INSPECTION-NEED PROTECTION FOR M/C, FLEX 300.4 4) JUNCTION BOXES AND VDV SPLICES TO BE ACCESSIBLE 5) SUPPORT RACEWAYS PER CODE 358.30 6) PREVENT DIELECTRIC CONTACT 7) HAVE QUALIFIED ELECTRICIAN PRESENT ON JOB TO ANSWER QUESTIONS 8) INSPECTION STOPPED |
|
09/07/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BE ADVISED WIRING/BOXES OUTSIDE ENTRY DOOR WEST SIDE NOT RATED FOR OUTSIDE USE 2) EAST AND SOUTH KITCHEN WALL COVERED PRIOR TO INSPECTION, UNCOVER. ALSO FLEX CONDUIT NOT ATTACHED TO BOX AND MC NEEDS NAIL PLATES, BAR NOT COMPLETE 3) J-BOXES IN SOFFITS TO HAVE ACCESS 4) CONDUITS IN RESTROOM NEEDS TO BE AGAINST STUD (FLAT) FOR STRAPS TO BE EFFECTIVE |
|
09/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
08/30/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SUPPORT MC CABLE FLEX AND J-BOXES AND FLEX PER CODE. J-BOXES TO BE ACCESSIBLE 2) NEW WALLS/LIGHTING NORTH END OF BLDG NOT SHOWN ON PLAN |