Permit: T11CM01520

Parcel: 125170230


Addresses:

15 N ALVERNON WY


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T11CM01520

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/28/2011 ELECTRIC - INTERMEDIATE Approved
10/13/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/15/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS AND LIDS FOR DRYWALL
2) NOTE: BOX ACCESSIBILITY
09/14/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
1) FINISH PREVIOUS ITEMS WITH SHAFFER ELECTRIC
2) PLEASE PAY REINSPECTION FEE BEFORE NEXT INSPECTION
09/09/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) TIGHTEN LOOSE FITTINGS AND MISSING SET SCREWS
2) FILL UNUSED OPENINGS IN JUNCTION BOXES
3) UNCOVER ALL AREAS COVERED WITHOUT INSPECTION-NEED PROTECTION FOR M/C, FLEX 300.4
4) JUNCTION BOXES AND VDV SPLICES TO BE ACCESSIBLE
5) SUPPORT RACEWAYS PER CODE 358.30
6) PREVENT DIELECTRIC CONTACT
7) HAVE QUALIFIED ELECTRICIAN PRESENT ON JOB TO ANSWER QUESTIONS
8) INSPECTION STOPPED
09/07/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) BE ADVISED WIRING/BOXES OUTSIDE ENTRY DOOR WEST SIDE NOT RATED FOR OUTSIDE USE
2) EAST AND SOUTH KITCHEN WALL COVERED PRIOR TO INSPECTION, UNCOVER. ALSO FLEX CONDUIT NOT ATTACHED TO BOX AND MC NEEDS NAIL PLATES, BAR NOT COMPLETE
3) J-BOXES IN SOFFITS TO HAVE ACCESS
4) CONDUITS IN RESTROOM NEEDS TO BE AGAINST STUD (FLAT) FOR STRAPS TO BE EFFECTIVE
09/01/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/30/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SUPPORT MC CABLE FLEX AND J-BOXES AND FLEX PER CODE. J-BOXES TO BE ACCESSIBLE
2) NEW WALLS/LIGHTING NORTH END OF BLDG NOT SHOWN ON PLAN