Permit: T11CM01503

Parcel: 141190990

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/23/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
05/19/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE AN OVERFLOW SENSOR IN SECONDARY DRAIN OUTLET
2) EXTEND VENT ON CONDENSATE DRAIN ABOVE DRAIN PAN
3) 3/8" I.D. GAS FLEX NOT ADEQUATE FOR 100,000 BTU
4) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX