Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T11CM01486

Parcel: 12801005H

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T11CM01486

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/20/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/07/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE ECONOMIZERS FOR A/C UNITS PER PLANS
2) TOILET ROOM EXHAUST AND A/C UNIT FANS MUST RUN CONTINOUSLY DURING OCCUPIED HOURS
3) PROVIDE AIR BALANCE REPORT