Permit: T11CM01486

Parcel: 12801005H

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/20/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/07/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE ECONOMIZERS FOR A/C UNITS PER PLANS
2) TOILET ROOM EXHAUST AND A/C UNIT FANS MUST RUN CONTINOUSLY DURING OCCUPIED HOURS
3) PROVIDE AIR BALANCE REPORT