Permit: T11CM01479

Parcel: 128120790


Addresses:

4918 E 17TH ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
08/19/2011 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
08/17/2011 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) PROVIDE APPROVED VENTING OF WATER HEATER
2) CORRECT DRIPPING RELIEF VALVE, A FLEX IS NOT ALLOWED ON DRAIN
3) PROVIDE APPROVED GAS VALVES
4) SUPPORT EXTERIOR PIPING
5) PROVIDE A PROPERLY SIZED GAS FLEX TO NEW FURNACE
08/11/2011 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 10 PSI NEEDS TO HOLD 15 MINUTES