Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
Permit Number - T11CM01464
Inspection Description - EXCAVATION/LAYOUT REBAR & ZON
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/30/2012 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
| 08/05/2011 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLANS NEED TO SHOW WHAT IS DONE ON SITE (REVISION) 2) NEED SUPERVISORS PERMISSION TO TRY TO GET CLAYTON TO JOB SITE BEFORE PLAN REVISONS ARE MADE 3) MAX OVERCURRENT PROTECTION FOR 12 AWG IS 20 AMPS ON KITCHEN CIRCUIT 4) LOOSE NEUTRAL WIRE IN PANEL-BREAKER DBL LUGGED |
|
| 06/01/2011 | EXCAVATION/LAYOUT REBAR & ZON | Not ready for Inspection | IVRS - Inspection :* 1) NEED ELECTRIC UPGRADE AND RECONNECT ADDED TO PERMIT TO GET POWER TO EXPOSE FOOTINGS |
|
| 05/26/2011 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLANS DO NOT MATCH WHAT IS BUILT ON SITE 2) PLAN REVISION NEEDED |