Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/22/2011 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/14/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PROVIDE MINIMUM R-8 ON ALL DUCT WITHIN THE VENTED ABOVE CEILING SPACE 2) PROVIDE INSULATION ON CONDENSATE PIPING AS CALLED FOR ON PLANS 3) VERIFY INSULATION IN ROOF CURBS AS SHOWN IN DETAIL 3-MP2.0 BEFORE SETTING UNITS |