Permit: T11CM01459

Parcel: 10602299A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T11CM01459

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/28/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/27/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
06/24/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FINISH CEILING ROOM 102
2) BREAKER TO BE LISTED FOR USE BY MANUFACTURE
3) WHERE IS CEILING OUTLET PER PLANS ROOM 107
4) MISSING 3 EM LIGHTS
5) PANEL DIRECTORY
06/02/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK VDV IN WALLS
2) OK WALLS
05/31/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
SUPPORT VDV IN WALL 725.8
BOXES MOVING IN WALLS 314.23
OK EXCEPT UDV IN WALLS