Permit: T11CM01448

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T11CM01448

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
09/07/2012 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
11/05/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
11/04/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) AFTER HOURS INSPECTION REQUESTED BY JESSE WITH JE DUNN/BARKER MORRISEY $165.00 TO BE CHARGED TO BARKER MORRISEY
2) BLDG DRAIN REPLACEMENT PER REVISED P-102 WITH CONNECTIONS TO EXISTING 4" ? IN 2 LOCATIONS OK
3) CLEANOUTS AND WATER TESTS OK
11/03/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
NOTE: CODE DOES NOT ALLOW SDR 35 UNDER A BLDG. REPLACE SDR35 PIPING TO CONNECTION WITH APPROVED MATERIAL AT EXISTING CLEANOUT
11/02/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 10 AM INSPECTION REQUESTED, NOT READY. 12 NOON COURTESY REINSPECTION
2) 8" BLDG DRAIN REPLACEMENT INSALLED PER UNAPPROVED ADDENDUM AND 5.RFI72
3) WATER TEST OK
4) PROVIDE VERIFICATION OF GRADE AND CITY APPROVED PLAN REVISION
5) PLAN INDICATES 74 PERCENT SLOPE AND DOES NOT SHOW THE CODE REQUIRED CLEANOUTS NOT TO EXCEED 100' DEVELOPED LENGTH
11/01/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) GOOD PROGRESS
10/31/2011 PLUMBING - ROUGH, SOIL Partial Approval 1) LOCATE AND ? EXISTING 6" SEWER
2) REVIEWED AUTHORITY TO DISCHARGE
10/28/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
10/21/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 10" RWL WITHIN BLDG FOUNDATION, WITH TEST OK TO COVER
10/20/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) UNIFORM PLUMBING CODES (SEC. 712) REQUIRES A 10' WATER TEST WITH VISUAL INSPECTION OF EACH JOINT. PLASTIC MAY NOT BE TESTED WITH AIR (IPC 312)
10/18/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE DRAINAGE FITTINGS, USE PRIMER AND HEAVY BODY CEMENT