Permit: T11CM01443

Parcel: 116061870

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/26/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/19/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. ALL PVC PIPE IS TO HAVE PRIMERED JOINTS, PRIMER IS TO BE PURPLE IN COLOR, BLUE "HOT" GLUE IS NOT AN ALTERNATIVE TO PRIMER.
2. ALL PVC EXPOSED TO DAYLIGHT IS TO BE COATED FOR UV PROTECTION, VERTICAL AS WELL AS HORIZONTAL (IF THE PRINTING ON THE PIPE CAN STILL BE READ, THE COATING IS TOO THIN)
3. FUSES NOT IDENTIFIED
4. UNIT DATA PLATE NOT IDENTIFIED
5. PROVIDE APPROVED ROOF LOAD CALC.