Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T11CM01442

Parcel: 11619376A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/24/2012 MECHANICAL - FINAL Approved
02/02/2012 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) ERO-1 DUCT SMOKE DETECTOR TEST OK
2) FCU-6 DUCT SMOKE DETECTOR TEST OK
3) PROVIDE BALANCE REPORT, ALL LIFE SAFETY ISSUES HAVE BEEN ADDRESSED, SEE BLDG INSPECTOR FOR TCO
01/31/2012 MECHANICAL - FINAL Partial Approval DUCT SMOKE TEST ON FCU-16, AHU-4
FCU-6 NOT RUNNING - FAILED