Permit: T11CM01442

Parcel: 11619376A

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
02/24/2012 MECHANICAL - ABOVE CEILING Approved
01/25/2012 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
01/23/2012 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) AIR HANDLERS 1, 2 AND 3 DUCT SMOKE DETECTOR TEST OK
01/20/2012 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) FCU-7A OK, 7B OK, 7C OK AND 7D OK
2) FCU-6 FAILED
3) FCU-8A OK AND FCU 8B OK
01/18/2012 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) DUCT SMOKE DETECTOR TESTING ON THE FOLLOWING UNITS FCU-11 OK & AHU-1, AHU-2, AHU-3 AND ERU-1 NOT OPERATIONAL
2) V.S.F. DUCT ABOVE CEILING OK TO COVER
3) ALL OF ANNEX DUCT ABOVE CEILING OK TO COVER
4) ALL ROOF TOP EQUIPMENT OK
5) EF-9 AND EF-10 OK
6) BOILER FLUE (STEAM GENERATOR) OK THRU ROOF
01/17/2012 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
01/03/2012 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
12/12/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
11/30/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ROOM A101 B OK, A122 A & B AND LOADING DOCK
11/29/2011 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
11/22/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) 2ND FLOOR OK
11/18/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ? DAY ROOM 2ND FLOOR
11/15/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) DUCT AND PIPING (HYDRO) ABOVE CEILING IN ROOMS 212, 214, 215E, 215B, 215H, 215G, 218, CORRIDORS 211, 212, 208 OK TO COVER
2) HYDRO TEST ON 1ST & 2ND FLOORS OK EXCLUDING MECH ROOMS
11/14/2011 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
11/10/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) DUCT AND PIPING ABOVE CEILING IN ROOMS 201 THRU 211, 215C, 215D, 215I, 216, 219, 221 A & B, 222 A & B, 223 THRU 227 AND CORRIDORS 215 & 216 OK TO COVER
11/09/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) CHWS/R HYDRO ON ALL THREE FLOORS OK, OK TO INSULATE
2) DUCT AND PIPING ABOVE CEILING 1ST FLOOR OK TO COVER
11/08/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
11/03/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) 2ND FLOOR LARGE AREA NORTHWEST (201), (202) AND ADJOINING OFFICES DUCT ABOVE CEILING OK TO COVER
10/31/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) MAKE CORRECTIONS AS INDICATED ON PLAN SHEET (FIELD SET)
10/28/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE SECONDARY DRAINS ON FCS
2) INSULATE HYDRO PIPING
10/21/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) RESTROOM A-106 DUCT ABOVE HARD LID OK TO COVER ALSO RESTROOMS AT A-115
09/23/2011 MECHANICAL - ABOVE CEILING Partial Approval DUCT ABOVE HARD LID 3RD FLOOR RESTROOMS OK TO COMPLETE
09/15/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) 2ND FLOOR HARD LID DUCT OK TO COVER
09/13/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/26/2011 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*