Permit: T11CM01442

Parcel: 11619376A

Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Date Description Inspector Results Comments
02/24/2012 ELECTRIC - PROGRESS Approved
01/27/2012 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
01/26/2012 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) DISCONNECTING MEANS AT ? DOOR MOTOR
2) NEED BOND JUMPERS (SAME SIZE) LIGHTING CONDUCTORS
3) FILL UNUSED OPENINGS IN LIGHTS SHOP
4) OK ROOMS #104B; 101 A, B & C; 102-104, 120A, B, C & D; 121, 117, 116, C128, FOR TRIM; 115A, B, C, D, E & F; 118, 119 AND 137; EXCEPT AS NOTED
01/25/2012 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) SPACE LED POWER SUPPLIES OFF OF DRYWALL DUE TO HEATING
2) OK 3RD FLOOR TRIM ANNEX "A"
3) OK PVC BOLLARDS IN BRIDGE
4) OK PVC WEST GATES
01/23/2012 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
3RD FLOOR:
1) BOND PLUG STRIP BACK PLATE
2) USE APPROVED HARDWARE
3) LOOSE FITTINGS
4) FINISH 3RD FLOOR
5) OK 2ND FLOOR TRIM AREA "A"
01/18/2012 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK DISC. SW. FOR FIRE PUMP
2) TRIM 1ST FLOOR AREA "A"
3) OK EAST GATE LOWERED CONDUITS 1 & 3
01/10/2012 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
01/06/2012 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1ST AND 2ND FLOOR:
1) RECEPT SCREWS 406.3
2) FILL UNUSED OPENINGS (VDV BOXES AND CABINETS)
3) FINISH ROOMS
NOTE: CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8
01/05/2012 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) BOXES MORE THAN 1/4" OR 1/8" 314.20 AND 21
2) CHECK DISCONNECTING MEANS INSTA HOTS
3) CHECK PLUG MOLD
4) (CLIMATIC) LOOSE FITTINGS
5) BOND BUSHINGS 250.97
6) LABEL DISCONNECTS
7) OK POLE HEAD MAKEUP 42 POLES
01/04/2012 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
12/19/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK CADWELDS LIGHTING SYSTEM NORTH SIDE
12/13/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) PLEASE CALL LEERAY TO RESOLVE THIS ISSUE, OR RICK HOLLANDER WILL BE BACK THURSDAY 12/15/11
12/07/2011 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
11/22/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) AS PER IBC 2702.1.1 GENERTOR IS TO BE LISTED. MODEL NUMBER ON GENERATOR IS NOT ON UL ON LINE CERTIFICATION DIRECTORY. IT APPEARS UNIT DOES NOT COMPLY WITH UL 2200.12.2 AND 12.2.1. A NRTL FIELD TEST MAY BE NECESSARY TO CONFIRM COMPLIANCE
2) OK ROOMS 107, 109, 111, 113, 215 A, B, C, D, F, G, H AND I
11/21/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK POLE BASE AS MARKED
2) OK CORRIDOR C112, C113, C103, C117 AND C118
3) OK UFD AND STARTER-HHPP, HHSP AND B1 & B2
11/19/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK PANELS TO MAIN: RPND, RPEM, RPT111A, RPTH1B, RPTFR, T30-101, T3E-101, RIN-B01. L3E, B01, R1E-201, RPS95, RPSQ4, L131-301, RPTR OK BUSS PLUGS AS GREEN STICKER MARKED
2) CLEAN FOREIGN MATERIAL AND DIRT FROM PANELS
3) FILL UNUSED OPENINGS
4) MARKING TAPT TO ENCIRCLE
5) TIGHTEN LUG CONNECTIONS
6) ? UPS RUN UNDER SIZED
7) SECURE UPS ?
11/18/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) NEED TO VERIFY GENERATOR LISTING
2) FINISH BOXES MAKE UP
3) OK A3E, A3L
4) OK ROOM 221A, EXCEPT AS NOTED
5) OK POLE BASE AS MARKED
11/17/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
11/10/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) BOX ABOVE GRID 130C
2) OK ROOMS 130C, 130A, 130 B AND 127
3) OK POLE BASE AS MARKED
4) OK LIGHTING AS MARKED
11/09/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
11/08/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
11/07/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
11/03/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) 5 LIGHT POLES GROUND OK NORTHWEST AREA
10/24/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8
2) FINISH BOXES ABOVE DOORS
3) PLEASE VERIFY PLENIUM RATING OT TY WRAPS FOR FIRE ALARM CABLES
4) OK POLE BASES AS MARKED
5) OK ROOMS 141, 104, 136, 135, 106, 133 B & A, 101, 102, 108 A, B, C, F & G AND 110 EXCEPT AS NOTED
6) FINISH VDV
10/21/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
10/19/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) ONLY ONE CONDUCTOR PER TERMINAL AND INSTALL PER INSTRUCTIONS (POLE BASE)
2) FILL UNUSED AREAS AT BOTTOM OF PANELS WITH A NON COMBUSTIBLE
3) TIGHTEN CABLE LASHINGS
4) OK STAIRWELL 2 WALLS, OK STAIRWELL 4 & 3 CAN IN LIDS, OK BATHROOM A105 AND A106, OK PANEL P3E-B01 TO MAIN AND AS MARKED, OK PSN-B01, OK POLE TO POLE AS MARKED AND OK 3 POLE BASES AS MARKED
10/17/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) CONDUCTOR TO ENTER VERTICAL SECTION SERVED 408.3
2) WILL NEED GFCI TEST ON ALL 1000 AMP 215.10
3) OK 1" POLE TO POLE AS MARKED
10/14/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
10/13/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK POLE TO POLE AS MARKED
10/06/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK 1' PVC POLE TO POLE AS MARKED
10/03/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
09/30/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK WALLS C126, 127, 128 & A107
2) 725.8, 760.24, 800.8 & 300.11 WILL APPLY
09/29/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK COMMUNICATION DUCT BANK A TO OUTSIDE PULL BOX 100'
2) OK WALLS ROOMS A107 (S), C126 AND 115A-E
3) ANSWERED QUESTIONS FOR WORKING CLEARANCE ELEVATOR DISCONNECTS
09/26/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
09/23/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK WALLS C125, 122A & B NORTH & EAST, A-122C
OK LV LIGHTING CONDUTER LOBIES 1 & 2
OK COMMUNICATION DUCT BANK A-B
09/22/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
09/21/2011 ELECTRIC - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DISCUSSED SERVICE
2) TIGHTEN LOOSE FITTINGS-CL1MADC
3) AREAS COVERED WITHOUT INSPECTION 3RD FLOOR-UNCOVER
4) INSPECTION STOPPED
09/14/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK WALLS VEHICLE SCREENING FACILITY
09/06/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
08/30/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
08/26/2011 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
1) NEED SUPPORTS THROUGHOUT, SEAL PENETRATIONS THRU FLOORS AND RECALL WHEN READY
08/22/2011 ELECTRIC - PROGRESS Partial Approval OK WALLS 141, 123 C & G, C101, C102, 127
08/18/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK EXCEPT 141, 123 C & G, C101, C102, 127
2) 115 A, B, C AND D ON 1ST FLOOR AREA "A" WALLS
07/20/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*