Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/01/2012 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/20/2012 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 01/17/2012 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) LOWER GARAGE FAN COILS 1-8, ? PUMPS 1 & 2, T3N C02, RIN C01, L3N C01 |
|
| 01/10/2012 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PVC CONDUITS AT GATE BARRIERS TO BE PER 308.5 |
|
| 01/04/2012 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) MAINTAIN WORKING SPACE AT FIRE PUMP 2) OK EMPLOYEE LOBBY CEILING |
|
| 12/14/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) ? CHARGERS-2 UNITS (UL) LISTED 2) EMCP=ENGINE MONITOR CONTROL PANEL=OVER/UNDER VOLTAGE (CSA). VOLTAGE REGULATOR=CDVR (CSA) ?, GENERATOR-(UL) LISTED 3) CAT REP WILL SEND START UP REPORT TO LEERAY 4) 1ST FLOOR #115 A, B, C AND D 5) 3RD FLOOR T3N & T3S LEAVE TILES OPEN FOR WINDOW BLIND MOTORS 6) CKT BREAKERS (UL) LISTED 7) CATAPILLAR TO INSTALL BARRIER AT BOTTOM OF TERM CAN |
|
| 12/06/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 12/05/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) ROOMS 310 C & B |
|
| 12/02/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) ROOMS #316 & 311 |
|
| 12/01/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) ROOMS #331, 331B, 325 A B C, 327 A & B, 318 AND 322 3 TRANSFORMER, 3TN-201, 3TS201 |
|
| 11/30/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) ROOMS 301, 302, 304, 305, 310 A & B, 311, 337, 339, 341, 342 AND 343 OK |
|
| 11/29/2011 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 11/28/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) ROOMS 224, 225, 226, 227, 215E, 215, 215I, A121 AND 122X |
|
| 11/22/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 11/21/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 11/18/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 11/17/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 11/15/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH BOX MAKE UP 2) FINISH VDV CABLING 3) VERIFY BOX FILL 4) OK CORRIDORS Q115, C117 EXCEPT AS NOTED |
|
| 11/10/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 11/09/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK LIGHTING AS MARKED 2) OK POLE BASES AS MARKED 3) OK CORRIDORS C121, 123 * 119 4) OK ROOM 133A, 135, 136 5) SUPPORT WIRES NEEDED FOR EXIT SIGNS-CITY AMENDMENTS |
|
| 11/08/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) BOND AT CONCENTRICS 250V 256.97 ROOF: 1) RECEPTS TO BE WEATHER PROOF WHETHER OR NOT PLUGGED INTO 406.8 3) OK ROOMS 108 A-E AND 110 4) OK LIGHTING GROUND RING CADWELDS AND GROUND RODS AS MARKED |
|
| 11/07/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FILL UNUSED PORTION OF OPENINGS FIXTURES AND BOXES 2) OK BUSS SUPPORTS |
|
| 11/03/2011 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 10/27/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK BATHROOMS 123B AND F |
|
| 10/26/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK POLE BASES AS MARKED |
|
| 10/25/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 10/24/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 10/21/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH VDV CABLING TO INSPECT 2) FINISH FAN COILS 3) SECURING METHODS TO BE PLENIUM RATED 4) OK POLE BASES AS MARKED 5) OK 6-1" PVC OUT 40' EAST 6) OK 2-3" PVC OUT 70' EAST THEN NORTH 7) OK TO POLE TO POLE AS MARKED 8) PROPERLY INSTALL EXTENSION BOX AND NEED ARC SHIELD 314.20 9) FIXTURES TO BE SECURELY ATTACHED TO GRID 410.16 |
|
| 10/19/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |