Permit: T11CM01442

Parcel: 11619376A

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
02/01/2012 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/20/2012 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
01/17/2012 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) LOWER GARAGE FAN COILS 1-8, ? PUMPS 1 & 2, T3N C02, RIN C01, L3N C01
01/10/2012 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PVC CONDUITS AT GATE BARRIERS TO BE PER 308.5
01/04/2012 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) MAINTAIN WORKING SPACE AT FIRE PUMP
2) OK EMPLOYEE LOBBY CEILING
12/14/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ? CHARGERS-2 UNITS (UL) LISTED
2) EMCP=ENGINE MONITOR CONTROL PANEL=OVER/UNDER VOLTAGE (CSA). VOLTAGE REGULATOR=CDVR (CSA) ?, GENERATOR-(UL) LISTED
3) CAT REP WILL SEND START UP REPORT TO LEERAY
4) 1ST FLOOR #115 A, B, C AND D
5) 3RD FLOOR T3N & T3S LEAVE TILES OPEN FOR WINDOW BLIND MOTORS
6) CKT BREAKERS (UL) LISTED
7) CATAPILLAR TO INSTALL BARRIER AT BOTTOM OF TERM CAN
12/06/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
12/05/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ROOMS 310 C & B
12/02/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ROOMS #316 & 311
12/01/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ROOMS #331, 331B, 325 A B C, 327 A & B, 318 AND 322 3 TRANSFORMER, 3TN-201, 3TS201
11/30/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ROOMS 301, 302, 304, 305, 310 A & B, 311, 337, 339, 341, 342 AND 343 OK
11/29/2011 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
11/28/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ROOMS 224, 225, 226, 227, 215E, 215, 215I, A121 AND 122X
11/22/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
11/21/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
11/18/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
11/17/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
11/15/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) FINISH BOX MAKE UP
2) FINISH VDV CABLING
3) VERIFY BOX FILL
4) OK CORRIDORS Q115, C117 EXCEPT AS NOTED
11/10/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
11/09/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK LIGHTING AS MARKED
2) OK POLE BASES AS MARKED
3) OK CORRIDORS C121, 123 * 119
4) OK ROOM 133A, 135, 136
5) SUPPORT WIRES NEEDED FOR EXIT SIGNS-CITY AMENDMENTS
11/08/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) BOND AT CONCENTRICS 250V 256.97
ROOF:
1) RECEPTS TO BE WEATHER PROOF WHETHER OR NOT PLUGGED INTO 406.8
3) OK ROOMS 108 A-E AND 110
4) OK LIGHTING GROUND RING CADWELDS AND GROUND RODS AS MARKED
11/07/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) FILL UNUSED PORTION OF OPENINGS FIXTURES AND BOXES
2) OK BUSS SUPPORTS
11/03/2011 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
10/27/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK BATHROOMS 123B AND F
10/26/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK POLE BASES AS MARKED
10/25/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
10/24/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
10/21/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) FINISH VDV CABLING TO INSPECT
2) FINISH FAN COILS
3) SECURING METHODS TO BE PLENIUM RATED
4) OK POLE BASES AS MARKED
5) OK 6-1" PVC OUT 40' EAST
6) OK 2-3" PVC OUT 70' EAST THEN NORTH
7) OK TO POLE TO POLE AS MARKED
8) PROPERLY INSTALL EXTENSION BOX AND NEED ARC SHIELD 314.20
9) FIXTURES TO BE SECURELY ATTACHED TO GRID 410.16
10/19/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*