Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2011 | BUILDING - FINAL | Approved | IVRS - Inspection :* ECO CLEARED FOR "PHOTOVOLTAIC SYSTEM" ON 7/15/11 |
|
| 07/11/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDING ELECTRODE BONDING STILL MISSING 250.64 |
|
| 06/20/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LABEL ON 30 AMP BREAKER ON MAIN PANEL MISSING 690.17 2) GROUNDING ELECTRODE TO BE BONDED ON BOTH ENDS WHEN RUN IN EMT PIPE 250.64 3) CONNECTOR ON METER BASE TO DISCONNECT, CONNECTOR ON INVERTER DISCONNECT, LB-T ON ROOF & FIRST BOX CONNECTORS LOOSE 4) BOLTS FOR STANDS AND STRUT TO HAVE SEALENT 5) GROUND SCREW IN BELL BOX TO BE GREEN MACHINE SCREW NOT A SELF TAPER TO EAST 6) COUPLINGS FOR PANEL RAILS TO BE BONDED OR SHOW INSTRUCTIONS TELLING YOU NOT TO 7) LADDER TO BE TIED OFF FOR INSPECTION ON ROOF 8) STAND OFF'S NOT TO PRINT-WHY ? |