Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T11CM01377
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2011 | BUILDING - FINAL | Approved | IVRS - Inspection :* 1) MARK JR. TO FIX CORRECTIONS |
|
| 07/28/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE NOTES LAST INSPECTION |
|
| 07/25/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TIGHTEN LOOSE FITTINGS 2) GROUNDING ELECTRODE CONDUCTOR TO BE MINIMUM #8 250.66 3) INSTALL GROUNDING ELECTRODE CONDUCTOR PER 250.64 4) REFERENCE TO 230.46 INCORRECT. THIS IN A LINE SIDE TAP 5) HAVE LADDER TIED OFF FOR ROOF ACCESS |