Permit: T11CM01377

Parcel: 105095710

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T11CM01377

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/01/2011 BUILDING - FINAL Approved IVRS - Inspection :*
1) MARK JR. TO FIX CORRECTIONS
07/28/2011 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEE NOTES LAST INSPECTION
07/25/2011 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TIGHTEN LOOSE FITTINGS
2) GROUNDING ELECTRODE CONDUCTOR TO BE MINIMUM #8 250.66
3) INSTALL GROUNDING ELECTRODE CONDUCTOR PER 250.64
4) REFERENCE TO 230.46 INCORRECT. THIS IN A LINE SIDE TAP
5) HAVE LADDER TIED OFF FOR ROOF ACCESS