Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T11CM01376
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/06/2011 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
08/25/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INVERTER GROUNDING ELECTRODE TO #8 NOT #10 |
|
08/24/2011 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/19/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDING TO INVERTERS RAILS TO BE #8 WIRE SIZE 2. STANDOFF LEGS TO SOLAR PANELS LOOSE |