Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T11CM01374
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/13/2011 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) FOR FINAL PROVIDE AIR BALANCE REPORT FOR ALL SYSTEMS PER PLANS 2) NEED TO TEST DUCT SMOKE DETECTION SYSTEM |
|
06/10/2011 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE ACCESS TO FC 1-3 AND 1-5 2) INSTALL DUCT SMOKE DETECTORS IN PROPER LOCATION AT UNITS FC 1-1,1-3 AND 1-5 3) INSULATE SUPPLY ELBOWS AT GRILLS |
|
06/09/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) ABOVE CEILING OK SOUTH HALF OF BLDG 2) STILL NEED TO SEE FIRE WRAP ON ABS PIPING 3) ALL DUCT SMOKE DETECTORS MUST BE CONNECTED TOGETHER WITH AUDIBLE AND VISIBLE ALARMS WHEN MULTIPLE FOR COILS SHARE THE SAME RETURN PLENIUM-SEE ENGINEER |