Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T11CM01374

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/13/2011 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) FOR FINAL PROVIDE AIR BALANCE REPORT FOR ALL SYSTEMS PER PLANS
2) NEED TO TEST DUCT SMOKE DETECTION SYSTEM
06/10/2011 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) PROVIDE ACCESS TO FC 1-3 AND 1-5
2) INSTALL DUCT SMOKE DETECTORS IN PROPER LOCATION AT UNITS FC 1-1,1-3 AND 1-5
3) INSULATE SUPPLY ELBOWS AT GRILLS
06/09/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ABOVE CEILING OK SOUTH HALF OF BLDG
2) STILL NEED TO SEE FIRE WRAP ON ABS PIPING
3) ALL DUCT SMOKE DETECTORS MUST BE CONNECTED TOGETHER WITH AUDIBLE AND VISIBLE ALARMS WHEN MULTIPLE FOR COILS SHARE THE SAME RETURN PLENIUM-SEE ENGINEER