Permit: T11CM01371

Parcel: 11703180A


Addresses:

325 W 2ND ST 01

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
10/31/2011 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
10/14/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ITEMS 1 & 2 DATED 10/7/11 HAVE BEEN CORRECTED, COMPLETE INSTALLATION OF REGISTERS FOR ABOVE CEILING APPROVAL
10/07/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ALL JOINTS IN DUCT WORK ARE TO BE SEALED PER MECH SPEC M4.1 GALVANIZED DUCT WORK
2) ALL CONDENSATE PIPING TO BE COPPER WITH 1/2" ARMAFLEX INSULATION PER MECH SPECS M4.1 CONDENSATE DRAIN PIPING
3) ALL CHANGES TO PLANS REQUIRE WRITTEN APPROVAL FROM ENGINEER