Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - FINAL
Permit Number - T11CM01364
Inspection Description - FIRE - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/17/2011 | FIRE - FINAL | Denied | Exit sign was not moved. Gave cell number for him to call me back later today. | |
11/17/2011 | FIRE - FINAL | Approved | ||
11/16/2011 | FIRE - FINAL | Denied | 1. Rear egress door shall have a thumb style dead bolt lock installed can not have double cylinder keyed dead bolt lock. 2. Remove cross bar hooks on rear egress door only install approved type locks on any egress door. 3. Sprinkler head blocked in hallway by exit sign, move head 3 feet away from sign or install sign on wall. 4. Install missing escutcheons in all closets. 5. 2nd rear egress door is covered up on the inside therefore will need to post on the outside the following wording "THIS DOOR BLOCKED" ¾ inch stroke by 6 inch high letters on a contrasting background as stated on the approved plans. |