Permit: T11CM01364

Parcel: 13355230A


Addresses:

9565 E 22ND ST #143


Inspection Status: Denied

Inspection History: FIRE - FINAL

Permit Number - T11CM01364

Inspection Description - FIRE - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
11/17/2011 FIRE - FINAL Denied Exit sign was not moved. Gave cell number for him to call me back later today.
11/17/2011 FIRE - FINAL Approved
11/16/2011 FIRE - FINAL Denied 1. Rear egress door shall have a thumb style dead bolt lock installed can not have double cylinder keyed dead bolt lock.
2. Remove cross bar hooks on rear egress door only install approved type locks on any egress door.
3. Sprinkler head blocked in hallway by exit sign, move head 3 feet away from sign or install sign on wall.
4. Install missing escutcheons in all closets.
5. 2nd rear egress door is covered up on the inside therefore will need to post on the outside the following wording "THIS DOOR BLOCKED" ¾ inch stroke by 6 inch high letters on a contrasting background as stated on the approved plans.