Permit: T11CM01364

Parcel: 13355230A


Addresses:

9565 E 22ND ST #143


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T11CM01364

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/16/2011 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
10/27/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PLANS REQUIRE A 1 HOUR SHAFT AROUND EXHAUST DUCT IN MED GAS ROOM
2) FIRE MASTER WRAP IS NOT AN OPTION
3) EXTEND BATHROOM EXHAUST DUCT UP INTO T-TOP
4) REPAIR DUCT INSULATION ON ELBOW ABOVE CORRIDOR
5) OK FOR PARTIAL TILES