Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T11CM01364
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/16/2011 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/27/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PLANS REQUIRE A 1 HOUR SHAFT AROUND EXHAUST DUCT IN MED GAS ROOM 2) FIRE MASTER WRAP IS NOT AN OPTION 3) EXTEND BATHROOM EXHAUST DUCT UP INTO T-TOP 4) REPAIR DUCT INSULATION ON ELBOW ABOVE CORRIDOR 5) OK FOR PARTIAL TILES |