Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - MEDICAL GAS/FINAL
Permit Number - T11CM01364
Inspection Description - PLUMBING - MEDICAL GAS/FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/21/2011 | PLUMBING - MEDICAL GAS/FINAL | Approved | IVRS - Inspection :* | |
09/08/2011 | PLUMBING - MEDICAL GAS/FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SUPPORT VAC PIPING CONTINOUSLY WITH SLOPE SPECIFIED 2) PROVIDE A VACUUM TEST ON PVC VAC PIPING 5.3.12.4.2 NOT SIZED PER PLAN NOTE: 1) COPPER AIR LINES REQUIRE A NITROGEN PURGE. AIR LINES WERE INSTALLED PRIOR TO PRE-CON MEETING AND WITH NO EVIDENCE OF REQUIRED PURGE 2) TYPE L HARD COPPER SPECIFIED FOR AIR LINES 3) CALL FOR A MED GAS PRE-CON PRIOR TO INSTALLING ANY GAS SYSTEM, 3RD PARTY VERIFICATION REQUIRED |