Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 05/11/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE GRAVITY DRAIN TO EXTERIOR OF STRUCTURE FOR PRESSURE RELIEF 2) PROVIDE WEATHER RESISTANT SCREWS FOR CLAMPS ON ROOF 3) INSULATION TO BE PROPERLY SEALED WITH NO VOIDS AND PROTECTED FROM UV EXPOSURE ON ROOF 4) SUPPORTS FOR ROOF TOP PIPING TO BE MASTIC TO ROOF AND AT CORRECT INTERVALS PROPERLY SECURED TO PIPING 5) PROVIDE CORRECT CLAMPS FOR PIPE SIZING 6) PROVIDE PLUG FOR WATER HEATER DRIP PAN 7) REMOVE ALL TAPE FROM VENT CONNECTORS AND PROVIDE FASTENERS AT VENT CONNECTOR JOINTS 8) WATER HEATER REQUIRES DBL WALL THRU CEILING AND ROOF TO POINT OF TERMINATION MINIMUM 3' ABOVE ANY AIR INTAKE WITH APPROVED VENT CAP AND WATER HEATER VENT PIPING WITHIN 10' OF AIR INTAKES 9) CONTRACTOR TO PAY REINSPECTION FEE |