Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T11CM01352
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/31/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
08/25/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* EXTEND ARMFLEX ON CONDENSORS SECTION LINE TO END OF PIPE. PROVIDE A PROTECTIVE COATING ON EXPOSED ARM FLEX PERMANENTLY ID ALL EQUIPMENT ON ROOF PROVIDE FUSES IN DISCONNECT PAINT ALL EXPOSED PLASTIC ON ROOF PROVIDE DUCT SMOKE DECTECTOR TEST REPORT EXTEND WATER HEATER INTAKE MIN 6" ABOVE ROOF BATHROOM EXHAUST AND A/C ? MUST RUN CONTINOUSLY DURING OCCUPIED HOURS |
|
08/22/2011 | MECHANICAL - FINAL | Not ready for Inspection | PROVIDE WATER HEATER CONDENSATE DRAIN |