Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T11CM01352
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/29/2011 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* 1) ABS APPROVED BY ARCHITECT 2) CORRECTIONS MADE OK-OK TO COVER |
|
06/28/2011 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1) INTER MEMBERING OF DISSIMILAR MATERIALS IS NOT ACCEPTED INSTALLATION STANDARD. ABS AND PVC ARE INCLUDED.TRANSITION CEMENT IS NOT APPROVED UNDER A BLDG. FURNACES NOT APPROVED. PLAN CALLS FOR PVC DWV 2) TRAP ARMS ARE ENGINEERED TO BE RUN AT 2 PERCENT. THE POINT OF VENT MAY NOT BE BELOW THE TRAP WEIR WHERE VENTS CONNECT TO A HORIZONTAL DRAIN, THEY SHALL HAVE THEIR INVERTS ABOVE THE DRAINAGE CENTER LINE |