Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T11CM01352

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
06/29/2011 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
1) ABS APPROVED BY ARCHITECT
2) CORRECTIONS MADE OK-OK TO COVER
06/28/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) INTER MEMBERING OF DISSIMILAR MATERIALS IS NOT ACCEPTED INSTALLATION STANDARD. ABS AND PVC ARE INCLUDED.TRANSITION CEMENT IS NOT APPROVED UNDER A BLDG. FURNACES NOT APPROVED. PLAN CALLS FOR PVC DWV
2) TRAP ARMS ARE ENGINEERED TO BE RUN AT 2 PERCENT. THE POINT OF VENT MAY NOT BE BELOW THE TRAP WEIR WHERE VENTS CONNECT TO A HORIZONTAL DRAIN, THEY SHALL HAVE THEIR INVERTS ABOVE THE DRAINAGE CENTER LINE