Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T11CM01352
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/31/2011 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
08/22/2011 | ELECTRIC - PROGRESS | Partial Approval | FINISH PREVIOUS ITEMS DISCUSSED | |
08/19/2011 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT SEAL TITE FOR A/C POWER PER CODES 2. ISOLATE POWER UP TO DISCONNECT ENCLOSURE IN A/C UNITS 3. MAINTAIN WORKING CLEARANCES 110.26 4. TIGHTEN LOOSE FITTINGS 5. NEED MAINTENANCE RECEPTACLES - 210.63 |
|
08/11/2011 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |