Permit: T11CM01352

Parcel: 105110700

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Permit Number - T11CM01352

Inspection Description - ELECTRIC - TEMPORARY SERVICE

Inspection Status - Approved

Date Description Inspector Results Comments
08/31/2011 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
08/18/2011 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection :*
08/17/2011 ELECTRIC - TEMPORARY SERVICE Not ready for Inspection IVRS - Inspection :*
08/16/2011 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
08/11/2011 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT M/C CABLES 330.30 & 300.11
2) SUPPORT VDV CABLING 725.8, 760.24, 800.24 & 300.11
3) SECURELY ATTACH FIXTURES TO GRID 410.16
4) FINISH BOX MAKE UP AND INSTALLING WIRING
5) CLEAN EXCESS DIRT AND FOREIGN MATERILA FROM PANELS 110.12
6) SEAL UNUSED RACEWAYS 110.12
7) DEVICES 8' AND BELOW TO BE PLUGGED, SWITCHED OR PLATED
8) ONLY ONE CONDUCTOR TO BREAKER TERMINAL 110.14
9) PROTECT CONDUCTORS AT FITTINGS 300.4
10) LOOSE CONDUCTOR TERMINATION
11) VERIFY BOX FILL
12) DO NOT TILE
08/10/2011 ELECTRIC - TEMPORARY SERVICE Not ready for Inspection IVRS - Inspection :*
08/03/2011 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection :*
1) POST BOND FOR TEMP POWER FOR TEST
2) VERIFY WATER, GAS, BLDG AND STEEL
3) LOCKOUT/TAGOUT