Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T11CM01352
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/31/2011 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
08/18/2011 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* | |
08/17/2011 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* | |
08/16/2011 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio |
|
08/11/2011 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT M/C CABLES 330.30 & 300.11 2) SUPPORT VDV CABLING 725.8, 760.24, 800.24 & 300.11 3) SECURELY ATTACH FIXTURES TO GRID 410.16 4) FINISH BOX MAKE UP AND INSTALLING WIRING 5) CLEAN EXCESS DIRT AND FOREIGN MATERILA FROM PANELS 110.12 6) SEAL UNUSED RACEWAYS 110.12 7) DEVICES 8' AND BELOW TO BE PLUGGED, SWITCHED OR PLATED 8) ONLY ONE CONDUCTOR TO BREAKER TERMINAL 110.14 9) PROTECT CONDUCTORS AT FITTINGS 300.4 10) LOOSE CONDUCTOR TERMINATION 11) VERIFY BOX FILL 12) DO NOT TILE |
|
08/10/2011 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* | |
08/03/2011 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* 1) POST BOND FOR TEMP POWER FOR TEST 2) VERIFY WATER, GAS, BLDG AND STEEL 3) LOCKOUT/TAGOUT |