Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T11CM01305
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/09/2011 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
12/08/2011 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
10/11/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) DUCT ABOVE CEILING OK TO COVER EXCEPT MAMMO ROOM, MRI AND MRI EQUIPMENT |
|
10/07/2011 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) SEISMIC RESTRAINT STRAPS ARE TO ATTACH TO MAIN GRID RUNNERS ONLY 2) PROVIDE O.B.D.'S PER PLANS 3) PROVIDE OVERFLOW PANS WITH E2 TRAPS PER PLANS |
|
08/26/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) DUCT ABOVE HARD LIDS OK TO COVER |
|
08/25/2011 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
08/24/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :*RECT. DUCT OK TO INSULATE |