Permit: T11CM01305

Parcel: 11615088L

Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Date Description Inspector Results Comments
10/08/2011 PLUMBING - ABOVE CEILING Approved IVRS - Inspection :*
09/16/2011 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) WATER PIPING MAY NOT PASS OVER ELECTRIC PANEL GAL. HANGER NOT APPROVED FOR COPPER
2) PIPING TO BE SUPPORTED AT EACH CHANGE OF DIRECTION
09/12/2011 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) INSULATION INCOMPLETE
2) HANGERS REQUIRED WITHIN 18" EACH SIDE OF N/H COMP, MAY NOT HAVE HANGER ON COUPLING
3) EQUIPMENT TO BE SUPPORTED SEPERATELY FROM PIPING
08/16/2011 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
08/10/2011 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) NEED TO SEE FLANGES
2) WALLS OK TO COVER S.T.O.I.
08/08/2011 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/03/2011 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) EXISTING PLUMBING OK TO COVER