Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T11CM01305
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/12/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK MRI ROOM, 116-121 ABOVE CEILING |
|
11/28/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK X-FORMER MAKE UP AND PANELS, A/C OK PER NOTE ON PLAN E-3 ELECTRIC ROOM |
|
11/23/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. GROUND ELECTRIC CONDUCTOR & BOND JUMPER NOT TO USE CAN AS PATH 2. VERIFY SERIES AIC RATINGS |
|
11/10/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS MRI ROOM 2) OK ABOVE CEILING 115, 125-128 AND 136 |
|
10/13/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK MAMO ROOM |
|
09/29/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK REDO WALL ROOM 115 2) OK CANS ROOM 125 3) SEAL UNUSED CONDUIT OPENING 4) NOT EQUIPMENT TO BE LISTED AND LABELED OR A NEUTRAL FIELD EVALUATION |
|
09/20/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALL NORTH SIDE OF ROOM 104 FOR CONTROL BOX |
|
09/12/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ? TRIP, PANEL X IN X RAY ? |
|
08/23/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OKAY EXCEPT MAMD BIOPSY |
|
08/11/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS EXCEPT MRI/CT XRAY 1 & 2 , BIOPSY AND MAMOGRAPHY |